Addr. Parameter C Setting Options Default Setting
Switching authority
_:150 U-def.FB ctl.#:Check
swi.auth. for Mode
•
no
•
yes
no
_:151 U-def.FB ctl.#:Swi.dev.
related sw.auth.
•
0
•
1
false
_:152 U-def.FB ctl.#:Specific
sw. authorities
•
0
•
1
true
_:115 U-def.FB ctl.#:Specific
sw.auth. valid for
•
station
•
station/remote
•
remote
station/remote
_:153 U-def.FB ctl.#:Num. of
specific sw.auth.
2 to 5 2
_:155 U-def.FB ctl.#:Ident.
sw.auth. 1
Freely editable text
_:156 U-def.FB ctl.#:Ident.
sw.auth. 2
Freely editable text
_:157 U-def.FB ctl.#:Ident.
sw.auth. 3
Freely editable text
_:158 U-def.FB ctl.#:Ident.
sw.auth. 4
Freely editable text
_:159 U-def.FB ctl.#:Ident.
sw.auth. 5
Freely editable text
_:154 U-def.FB ctl.#:Multiple
specific sw.auth.
•
0
•
1
false
Information List
No.
Information Data Class
(Type)
Type
U-def.FB ctl.#
_:503 U-def.FB ctl.#:>Sw. authority local SPS I
_:504 U-def.FB ctl.#:>Sw. authority remote SPS I
_:505 U-def.FB ctl.#:>Sw. mode interlocked SPS I
_:506 U-def.FB ctl.#:>Sw. mode non-interl. SPS I
_:51 U-def.FB ctl.#:Mode (controllable) ENC C
_:52 U-def.FB ctl.#:Behavior ENS O
_:53 U-def.FB ctl.#:Health ENS O
_:302 U-def.FB ctl.#:Switching auth. station SPC C
_:308 U-def.FB ctl.#:Enable sw. auth. 1 SPC C
_:309 U-def.FB ctl.#:Enable sw. auth. 2 SPC C
_:310 U-def.FB ctl.#:Enable sw. auth. 3 SPC C
_:311 U-def.FB ctl.#:Enable sw. auth. 4 SPC C
_:312 U-def.FB ctl.#:Enable sw. auth. 5 SPC C
_:313 U-def.FB ctl.#:Switching authority ENS O
_:314 U-def.FB ctl.#:Switching mode ENS O