[lovrkarc-130511-01.tif, 1, en_US]
Figure 7-52
Cyclic Reclosing Function: Logic for the Functions of Reduced Dead Time and Dead-Line Check
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:6601:1 General:Mode
off
on
test
on
_:6601:101 General:79 operating
mode
with op., w/o act. time
with op., with act. time
w.pickup, w/o act. time
w.pickup, w. action time
with op., with
act. time
7.2.4.19
Protection and Automation Functions
7.2 Automatic Reclosing Function
576 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017