No. Information Data Class
(Type)
Type
_:54 General:Protection inactive SPS O
_:323 General:LED reset SPC C
_:320 General:LED have been reset SPS O
Device Logoff
Overview
In the case of multibay functions, a device uses information from one or more other devices. For some applica-
tions, it may be necessary for you to remove a device with all effective functions temporarily from the plant
and even to switch it off. These applications are, for example:
Maintenance work
System upgrades
Testing the local protection functions
The
Device logoff
functionality informs the receiver devices about the imminent disconnection of the
transmitter devices. To do this, the last valid received information is stored in the receiver devices and used for
the multibay functions.
i
i
NOTE
If you need to remove a device temporarily from the plant, you must log off the device.
Protection functions distributed to several devices operate in a healthy manner with the remaining devices
only if you have logged off the device.
You can log off the device as follows:
Via the on-site operation panel
Via a communication interface using the
Device logoff
(
_:319
) controllable
Via the binary inputs, general:
>Device funct.logoff on
(
_:507
) or
>Dev. funct.logoff off
(
_:508
)
You can find the controllable and the binary inputs in the DIGSI 5 project tree under Name of the
deviceInformation routing in the working area in the General block.
During the log-off process, the device checks whether all conditions for a logoff have been met. If the condi-
tions for the log off have not been met, the logoff is rejected.
The logoff is rejected under the following conditions:
The devices are communicating via the protection interface and switching off the device leads to an
interruption in protection-interface communication.
i
i
NOTE
The option used to log the device off is stored in the operational log.
Even if you switch off the device after logoff, the
Device logged off
(_:315) state is stored.
If you want to establish the initial state again after logging off the device, you must log on the device again.
To log on the device, you must use the same option used for logoff. For example, if you have logged off the
device via binary inputs, you must log it on again via the binary inputs. This applies in similar manner if you
have logged off the device via DIGSI or via on-site operation.
3.10.3
3.10.3.1
System Functions
3.10 Device Settings
168 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017