has been exceeded. Either the frequency is out of range (10 Hz to 80 Hz) or the input signals are too small for
a manual update. Should this condition occur, the system switches the update frequency to a sampling rate
that corresponds to the rated frequency.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Phase sequence
•
ABC
•
ACB
ABC
General
_:8911:101 VT 3-phase:Rated primary
voltage
0.20 kV to 1200.00 kV 400.00 kV
_:8911:102 VT 3-phase:Rated secon-
dary voltage
80 V to 230 V 100 V
_:8911:103 VT 3-phase:Matching ratio
Vph / VN
0.10 to 9.99 1.73
_:8911:104 VT 3-phase:VT connection
•
not assigned
•
3 ph-to-gnd volt. + VN
•
3 ph-to-gnd voltages
•
3 ph-to-ph volt. + VN
•
3 ph-to-ph voltages
•
2 ph-to-ph volt. + VN
•
2 ph-to-ph voltages
•
2 ph-to-gnd volt. + VN
•
2 ph-to-gnd voltages
3 ph-to-gnd
volt. + VN
_:8911:106 VT 3-phase:Inverted phases
•
none
•
AC
•
BC
•
AB
none
_:8911:111 VT 3-phase:Tracking
•
inactive
•
active
active
_:8911:130 VT 3-phase:Measuring-
point ID
0 to 100 0
Voltage transformers1 - 4
_:3811:103 VT 1:Magnitude correction 0.010 to 10.000 1.000
_:3811:108 VT 1:Phase
•
V A
•
V B
•
V C
•
V AB
•
V BC
•
V CA
•
VN
•
Vx
General
_:8881:115 CT 3-phase:CT connection
•
not assigned
•
3-phase + IN
•
3-phase
•
3-phase + IN-separate
•
3-phase, 2 primary CT
•
3ph,2prim.CT + IN-sep
•
2ph, 2p. CT + IN-sep
•
2 phase + IN
3-phase + IN-
separate
5.1.6
Function-Group Types
5.1 Power-System Data
SIPROTEC 5, High-Voltage Bay Controller, Manual 189