EasyManua.ls Logo

Siemens 6MD85 - Settings; Information List

Siemens 6MD85
1256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings
Addr. Parameter C Setting Options Default Setting
General
_:6601:1 General:Mode
•
off
•
on
•
test
on
_:6601:101 General:79 operating mode
•
with op., w/o act. time
•
with op., with act. time
•
w.pickup, w/o act. time
•
w.pickup, w. action time
with op., with
act. time
_:6601:102 General:CB ready check bef.
start
•
no
•
yes
no
_:6601:103 General:Reclai. time
aft.succ.cyc.
0.50 s to 300.00 s 3.00 s
_:6601:104 General:Block. time aft.
man.close
0.00 s to 300.00 s 1.00 s
_:6601:105 General:Start signal
supervis.time
0.01 s to 300.00 s 0.13 s
_:6601:106 General:CB ready superv.
time
0.01 s to 300.00 s 3.00 s
_:6601:107 General:3-pole operate by
79
•
no
•
yes
yes
_:6601:111 General:Max. dead-time
extension
0.00 s to 300.00 s; ∞ 1.20 s
_:6601:114 General:Voltage supervi-
sion time
0.10 s to 30.00 s 0.10 s
_:6601:115 General:Volt. thres.f. live
line/bus
0.300 V to 340.000 V 48.000 V
ADT
_:6631:101 ADT:1-pole trip allowed
•
no
•
yes
no
_:6631:104 ADT:Action time 0.00 s to 300.00 s; ∞ 0.20 s
_:6631:105 ADT:Maximum dead time 0.50 s to 3000.00 s 5.00 s
_:6631:102 ADT:CB ready check
bef.close
•
no
•
yes
no
_:6631:103 ADT:Synchroch. aft. 3-pole
d.t.
•
none
•
internal
•
external
none
_:6631:106 ADT:Intern. synchrocheck
with
Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
General
_:6601:51 General:Mode (controllable) ENC C
_:6601:87 General:>Function off SPS I
_:6601:524 General:>Function on SPS I
_:6601:347 General:Function on SPC C
_:6601:82 General:>Block function SPS I
_:6601:501 General:>Release by ext.sync. SPS I
7.2.5.2
7.2.5.3
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 581
C53000-G5040-C015-9, Edition 11.2017

Table of Contents