EasyManua.ls Logo

Siemens 6MD85 - Settings

Siemens 6MD85
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter (End Supervision Group): Binary input
Default setting (_:109) Binary input = 1
Parameter Binary input is used to define the highest binary input for the last I/O module (see (_:108)
I/O module ID) that you want to assign to a supervision group.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 Superv.Grp.#:Mode
off
on
test
on
Superv. signal
_:104 Superv.Grp.#:I/O module
ID
I/O module 1
I/O module 2
I/O module 3
I/O module 4
I/O module 5
I/O module 6
I/O module 7
I/O module 8
I/O module 9
I/O module 10
I/O module 11
I/O module 12
I/O module 13
I/O module 14
I/O module 15
I/O module 1
_:105 Superv.Grp.#:Binary
input
1 to 256 1
_:102 Superv.Grp.#:Enable
variable group
0
1
false
Supervis. grp. start
_:106 Superv.Grp.#:I/O module
ID
I/O module 1
I/O module 2
I/O module 3
I/O module 4
I/O module 5
I/O module 6
I/O module 7
I/O module 8
I/O module 9
I/O module 10
I/O module 11
I/O module 12
I/O module 13
I/O module 14
I/O module 15
I/O module 1
_:107 Superv.Grp.#:Binary
input
1 to 256 1
8.3.3.5
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual 949
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD85

Related product manuals