Siemens recommends setting this time to 0 s so that it has no effect.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 Log.-inv.-T #:Mode
•
off
•
on
•
test
off
_:2 Log.-inv.-T #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:119 Log.-inv.-T #:Directional
mode
•
forward
•
reverse
forward
_:8 Log.-inv.-T #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:118 Log.-inv.-T #:Directional
comparison
•
no
•
yes
no
_:120 Log.-inv.-T #:Release via
input signal
•
no
•
yes
no
_:10 Log.-inv.-T #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:26 Log.-inv.-T #:Dynamic
settings
•
no
•
yes
no
_:27 Log.-inv.-T #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:3 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:6 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
_:113 Log.-inv.-T #:Min. time
of the curve
0.000 s to 60.000 s 1.200 s
_:114 Log.-inv.-T #:Max. time
of the curve
0.000 s to 60.000 s 5.800 s
_:116 Log.-inv.-T #:Threshold
multiplier
1.00 to 4.00 1.10
_:115 Log.-inv.-T #:Additional
time delay
0.000 s to 60.000 s 0.000 s
Dyn.s: AR off/n.rdy
_:28 Log.-inv.-T #:Effect. by
AR off/n.ready
•
no
•
yes
no
_:35 Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:29 Log.-inv.-T #:Effected by
AR cycle 1
•
no
•
yes
no
_:36 Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
7.7.7.3
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 733
C53000-G5040-C015-9, Edition 11.2017