Energy Values
Setting Values
Active energy W
p
kWh, MWh, GWh
Measuring range
Voltage range
Current range
Frequency range
|cosφ| ≥ 0.01
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned measuring
range
Frequency range (expanded) 40 Hz to 69 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rted
= 60 Hz
Tolerance 0.5 % of the measured value in the above mentioned measuring
range
Reactive energy W
q
kvarh, Mvarh, Gvarh
Measuring range
Voltage range
Current range
Frequency range
|cosφ| ≤ 0,984
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 1.0 % of the measured value in the above mentioned measuring
range
Frequency range (expanded) 40 Hz to 69 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 1.5 % of the measured value in the above mentioned measuring
range
11.47
Technical Data
11.47 Energy Values
SIPROTEC 5, High-Voltage Bay Controller, Manual 1199
C53000-G5040-C015-9, Edition 11.2017