EasyManua.ls Logo

Siemens 6MD85 - Group Indications of Overcurrent Protection Functions; Description

Siemens 6MD85
1256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Group Indications of Overcurrent Protection Functions
Description
The function block Group indications of the overcurrent protection functions uses the pickup and operate
indications of the following functions:
•
Overcurrent protection, phases
•
Overcurrent protection, ground
•
Directional overcurrent protection, phases
•
Directional overcurrent protection, ground
•
Ground-fault protection for high-impedance ground faults in grounded systems
•
Instantaneous high-current tripping
The group indications of the overcurrent protection are generated by a logical OR of the stage-selective pickup
and operate indications of the functions listed above (see also Figure 7-126):
•
Pickup
•
Operate
The pickup and operate indications are output, where present, with direction information.
[loocgrin-240112-01.tif, 3, en_US]
Figure 7-126
Logic Diagram of the Overcurrent Protection Group Indications
7.9
7.9.1
Protection and Automation Functions
7.9 Group Indications of Overcurrent Protection Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual 759
C53000-G5040-C015-9, Edition 11.2017