Addr. Parameter C Setting Options Default Setting
_:101 49 Th.overl. #:Threshold
current warning
1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:104 49 Th.overl. #:Threshold
thermal warn.
50 % to 100 % 90 %
_:105 49 Th.overl. #:Dropout
threshold operate
50 % to 99 % 90 %
_:112 49 Th.overl. #:Emerg.
start T overtravel
0 s to 15000 s 300 s
_:106 49 Th.overl. #:K-factor 0.10 to 4.00 1.10
_:110 49 Th.overl. #:Thermal
time constant
10 s to 60000 s 900 s
_:111 49 Th.overl. #:Cooling
time constant
10 s to 60000 s 3600 s
_:107 49 Th.overl. #:Imax
thermal
1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:108 49 Th.overl. #:Imin
cooling
1 A @ 100 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 100 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 50 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 50 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 2.500 A
_:109 49 Th.overl. #:Tempera-
ture rise at Irated
40 K to 200 K 70 K
_:113 49 Th.overl. #:Storage of
thermal replica
no
yes
no
_:114 49 Th.overl. #:Behav. at
I> Imax therm.
current limiting
freeze therm. rep.
current limiting
_:118 49 Th.overl. #:Default
temperature
-55°C to 55°C 40°C
_:117 49 Th.overl. #:Minimal
temperature
-55°C to 40°C -20°C
_:44 49 Th.overl. #:Tempera-
ture sensor
Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
49 Th.overl. #
_:51 49 Th.overl. #:Mode (controllable) ENC C
_:500 49 Th.overl. #:>Block stage SPS I
7.26.7
Protection and Automation Functions
7.26 Thermal Overload Protection, 3-Phase - Advanced
890 SIPROTEC 5, High-Voltage Bay Controller, Manual