Stage Setting Values
2 1.5 V
rated
0.1 s to 0.2 s
Settings
Addr. Parameter C Setting Options Default Setting
Definite-T 1
_:181:1 Definite-T 1:Mode
•
off
•
on
•
test
off
_:181:2 Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:181:9 Definite-T 1:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:181:8 Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:181:101 Definite-T 1:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:181:3 Definite-T 1:Threshold 0.300 V to 340.000 V 110.000 V
_:181:4 Definite-T 1:Dropout
ratio
0.90 to 0.99 0.95
_:181:6 Definite-T 1:Operate
delay
0.00 s to 300.00 s 3.00 s
Definite-T 2
_:182:1 Definite-T 2:Mode
•
off
•
on
•
test
off
_:182:2 Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:182:9 Definite-T 2:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:182:8 Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:182:101 Definite-T 2:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:182:3 Definite-T 2:Threshold 0.300 V to 340.000 V 130.000 V
_:182:4 Definite-T 2:Dropout
ratio
0.90 to 0.99 0.95
_:182:6 Definite-T 2:Operate
delay
0.00 s to 300.00 s 0.50 s
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:181:81 Definite-T 1:>Block stage SPS I
7.13.5
7.13.6
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual 787
C53000-G5040-C015-9, Edition 11.2017