No. Information Data Class
(Type)
Type
_:502 Syn./Asy.bal.#:>Start / stop syn.proc. SPS I
_:503 Syn./Asy.bal.#:>Start syn. process SPS I
_:504 Syn./Asy.bal.#:>Stop syn. process SPS I
_:506 Syn./Asy.bal.#:>Op. mode 'V1<V2>' SPS I
_:505 Syn./Asy.bal.#:>Op. mode 'V1>V2<' SPS I
_:507 Syn./Asy.bal.#:>Op. mode 'V1<V2<' SPS I
_:508 Syn./Asy.bal.#:>Op. mode 'dir.cls.cmd' SPS I
_:501 Syn./Asy.bal.#:>Block close command SPS I
_:511 Syn./Asy.bal.#:>Block balancing SPS I
_:513 Syn./Asy.bal.#:>Block V2 balancing SPS I
_:514 Syn./Asy.bal.#:>Block f2 balancing SPS I
_:54 Syn./Asy.bal.#:Inactive SPS O
_:52 Syn./Asy.bal.#:Behavior ENS O
_:53 Syn./Asy.bal.#:Health ENS O
_:328 Syn./Asy.bal.#:In progress SPS O
_:324 Syn./Asy.bal.#:Release close cmd. SPS O
_:305 Syn./Asy.bal.#:All sync. conditio. OK SPS O
_:303 Syn./Asy.bal.#:State f-synchronous SPS O
_:325 Syn./Asy.bal.#:Voltage difference OK SPS O
_:326 Syn./Asy.bal.#:Angle difference OK SPS O
_:327 Syn./Asy.bal.#:Frequency diff. OK SPS O
_:307 Syn./Asy.bal.#:Cond. V1<V2> fulfilled SPS O
_:306 Syn./Asy.bal.#:Cond. V1>V2< fulfilled SPS O
_:308 Syn./Asy.bal.#:Cond. V1<V2< fulfilled SPS O
_:309 Syn./Asy.bal.#:Frequency f1 > fmax SPS O
_:310 Syn./Asy.bal.#:Frequency f1 < fmin SPS O
_:311 Syn./Asy.bal.#:Frequency f2 > fmax SPS O
_:312 Syn./Asy.bal.#:Frequency f2 < fmin SPS O
_:313 Syn./Asy.bal.#:Voltage V1 > Vmax SPS O
_:314 Syn./Asy.bal.#:Voltage V1 < Vmin SPS O
_:315 Syn./Asy.bal.#:Voltage V2 > Vmax SPS O
_:316 Syn./Asy.bal.#:Voltage V2 < Vmin SPS O
_:317 Syn./Asy.bal.#:V dif.too large(V2>V1) SPS O
_:318 Syn./Asy.bal.#:V dif.too large(V2<V1) SPS O
_:319 Syn./Asy.bal.#:f dif.too large(f2>f1) SPS O
_:320 Syn./Asy.bal.#:f dif.too large(f2<f1) SPS O
_:329 Syn./Asy.bal.#:dfdiff/dt too large SPS O
_:321 Syn./Asy.bal.#:α dif.too large(α2>α1) SPS O
_:322 Syn./Asy.bal.#:α dif.too large(α2<α1) SPS O
_:304 Syn./Asy.bal.#:Max. time exceeded SPS O
_:323 Syn./Asy.bal.#:Setting error SPS O
_:332 Syn./Asy.bal.#:V2 control pulse higher SPS O
_:331 Syn./Asy.bal.#:V2 control pulse lower SPS O
_:334 Syn./Asy.bal.#:f2 control pulse higher SPS O
_:333 Syn./Asy.bal.#:f2 control pulse lower SPS O
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 407
C53000-G5040-C015-9, Edition 11.2017