Addr. Parameter C Setting Options Default Setting
_:2311:9 General:Measured value
•
3I0 calculated
•
IN measured
IN measured
General
_:781:1 Inverse-T 1:Mode
•
off
•
on
•
test
off
_:781:2 Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:781:26 Inverse-T 1:Dynamic
settings
•
no
•
yes
no
_:781:27 Inverse-T 1:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:781:8 Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:781:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:108 Inverse-T 1:Type of char-
acter. curve
_:781:113 Inverse-T 1:Min. time of
the curve
0.00 s to 1.00 s 0.00 s
_:781:109 Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:781:101 Inverse-T 1:Time dial 0.00 to 15.00 1.00
_:781:115 Inverse-T 1:Additional
time delay
0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:781:28 Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:781:35 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:781:29 Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:781:36 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:781:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:781:30 Inverse-T 1:Effected by
AR cycle 2
•
no
•
yes
no
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 653
C53000-G5040-C015-9, Edition 11.2017