EasyManua.ls Logo

Siemens 6MD85 - Page 727

Siemens 6MD85
1256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
Dyn.s: AR off/n.rdy
_:4891:28 Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:4891:35 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:4891:29 Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:4891:36 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:4891:30 Inverse-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:4891:37 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:4891:31 Inverse-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:4891:38 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:4891:32 Inverse-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:4891:39 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 727
C53000-G5040-C015-9, Edition 11.2017

Table of Contents