Commissioning
8.5 Commissioning with the STARTER commissioning tool
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
307
⇒ Under
n-controller act. val. selection
, select the encoder type or the other actual value
source:
● [0] Selection deactivated
● [1] Analog tachometer
● [2] Pulse encoder
● [3] EMF actual value internal
● [4] Free interconnection via p50609
● [5] DRIVE-CLiQ encoder
The drive cannot be operated if no selection is made.
⇒ Enter the
. To display on the AOP30 or to transfer the speed factors via
PROFIdrive, the physical speed at 100% is specified here.
The following settings are required, depending on the
n-controller act. val. selection
.
The analog tachometer is connected to the CUD via terminals XT1-103, XT1-104.
⇒ Enter the
tachometer voltage at maximum speed
.
⇒ Click
>
The pulse encoder is connected to the CUD via terminals X177:41 ... 48.
To select a predefined encoder configuration click on the radio button
Select standard
encoder from list
, and select one of the encoders that is listed.
The following encoder types can be evaluated via the CUD:
● [3001] 1024 HTL A/B R
● [3002] 1024 TTL A/B R
● [3003] 2048 HTL A/B R
● [3005] 1024 HTL A/B
● [3006] 1024 TTL A/B
● [3007] 2048 HTL A/B
● [3008] 2048 TTL A/B
● [3009] 1024 HTL A/B unipolar
● [3011] 2048 HTL A/B unipolar
⇒ To enter special encoder configurations, click the
radio button and then the
button. The following input screen is displayed for you to enter the required
data.