Descriptions of functions
10.3 Communication according to PROFIdrive
SINAMICS DCM DC Converter
446 Operating Instructions, 12/2018, A5E34763375A
Error values in DPV1 parameter responses
Table 10- 31 Error values in DPV1 parameter responses
Illegal parameter number.
Access to a parameter that does not exist.
0x01 Parameter value cannot be changed. Modification access to a parameter value that cannot be
Subindex
Lower or upper value limit exceeded.
Modification access with value outside value limits.
0x03 Invalid subindex. Access to a subindex that does not exist. Subindex
Access with subindex to non-indexed parameter.
0x05 Wrong data type. Modification access with a value that does not match the
data type of the parameter.
–
0x06 Illegal set operation (only reset
Modification access with a value not equal to 0 in a case
where this is not allowed.
Subindex
0x07 Description element cannot be
Modification access to a description element that cannot be
Subindex
0x09 No description data available. Access to a description that does not exist (the parameter
–
0x10 Read job will not be executed. The read request is refused because know-how protection is
Modification access with no operating priority.
0x0F No text array exists. Access to a text array that does not exist (the parameter
–
0x11 Request cannot be executed due to
Access is temporarily not possible for unspecified reasons. –
0x14 Illegal value. Modification access with a value that is within the limits but
is illegal for other permanent reasons (parameter with
defined individual values).
Subindex
0x15 Response too long. The length of the present response exceeds the maximum
–
0x16 Illegal parameter address. Illegal or unsupported value for attribute, number of
elements, parameter number, subindex or a combination of
–
Write request: Illegal or unsupported parameter data format.
0x18 Number of values inconsistent. Write request: A mismatch exists between the number of
values in the parameter data and the number of elements in
–
Drive object does not exist.
You have tried to access a drive object that does not exist.
Parameter text cannot be changed
Illegal or unknown request ID
0x65 Parameter presently deactivated. You have tried to access a parameter that, although
available, does not currently perform a function
(e.g. n control set and access to a V/f control parameter).
–