Stroke 20 mm 40 mm
Typical applications Stroke actuators Data Sheet Positioning force 800 N 1600 N
· Heating plants
· Ventilation and air conditioning
plants
· Heat generation
· Heat distribution
· District heating plants
SAX..
SAV..
8)
N4501
N4503
SAX.. SAV..
Valves Basic Doc. (P4030) Δp
max
[kPa]
Δp
max
[kPa]
Δp
max
[kPa]
Δp
max
[kPa]
Valves Data Sheet Valve type DN k
[m
3
/h]
PN16 N4403 VXF42.15-..
15 1.6 / 2.5 / 4
100
400
- -
VXF42.20-6.3
20 6.3
VXF42.25-..
25 6.3 / 10
VXF42.40-..
40 16 / 25
100 400VXF42.50-..
50 31.5 / 40 300
VXF42.65-..
65 50 / 63
50
150
VXF42.80-..
80 80 / 100 75
50
225
VXF42.100-..
100 125 / 160
- -
125
VXF42.125-..
125 200 / 250 90
-10…130 °C
VXF42.150-..
150 315 / 400 60
- -
VXF43.80-100 80 100
50
225
-20…130 °C
VXF43.150-400 150 400 60
200
1200
- -
VXF53.20-6.3 20 6.3
VXF53.25-..
25 6.3 / 10
VXF53.32-16 32 16 750
VXF53.40-..
40 16 / 25 500
200
1150
VXF53.50-40 50 40 100 300 700
PN25
VXF53.65-63 65 63
- -
100 400
50
-20…130 °C
VXF53.150-400 150 400
75
PN16 N4463 - VXG41.1301
15 1.6
-
800
- -
- VXG41.1401
15 2.5
VXG41.15 VXG41.1501
15 4
VXG41.20 VXG41.2001
20 6.3
VXG41.25 VXG41.2501
25 10
VXG41.32 VXG41.3201
32 16
VXG41.40 VXG41.4001
40 25 525
-25…130 °C
VXG41.50 VXG41.5001
50 40 300
1)
Insert running number instead of k
vs
value
2)
.. = insert k
vs
value
3)
With tight bypass; VXG41.1301 and VXG41.1401: use only SAX61.., SKD32.50 or SKD82.50.
4)
For media temperatures > 130 °C use electrohydraulic actuators SKD.. (N4561), SKB.. (N4564).
5)
Δp
max
= max. permissible differential pressure in diverting mode
6)
DN 15…50: Flange dimensions for PN 16 and PN 25
DN 65…150: Flange dimensions only for PN 25
7)
Valves no longer in the active sale
8)
SAV..: This product line of actuators might not be available in all countries. Please talk to your local
contact or consult your local internet pages of www.buildingtechnologies.siemens.com.