Installing, exchanging and connecting modules
Power supply
(150 W)
7
113 |
248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
The connection lines marked in bold of the additional cable tree (3) and the
existing cable tree (2) must be wired again when installing the second power
supply (slave).
In order to avoid operating temperature differences, the two power supply units
must be mounted next to each other in the same housing.
The batteries and the system supply must only be connected to the master
power supply unit.
Only one temperature sensor must be connected to the master power supply
unit.
The temperature sensor must be fitted close to the batteries. (You will find
precise details in document A6V10210390).
NOTICE
Damage to the power supply
Different versions (A4/A5) of the power supply (150 W) may not be switched in
parallel.