Mounting steps
WARNING
Heat bridge
between the station and mounting surface caused e.g.
by
overheating of the batteries
Danger of fire
If you mount the station on a flammable wall, all cut-out sections for the
mounting holes must be sealed using the supplied aluminium stickers.
1. Break out the required cable entries at the bottom of the rear panel and the
cover of the additional housing (4, 5), as well as the mounting holes for housing
assembly (3).
2. Attach edge protection strips or rubber grommets to the cable entries.
3. Fasten the rear panel of the additional housing (1) in the same way as that of
the station. Make sure that the alignment is exact.
4. Stick the supplied aluminium stickers over all holes for wall mounting.
5. Attach the two housings to one another by putting screws through the mounting
holes (3) in the bottom and the cover.
NOTICE
Battery leakage
Damage to hardware
If you assemble two housings one on top of the other, you fit the batteries in
the lower housing.
5.3 Connect the mains cable
5.3.1 Cable routing
Guidelines
The network cables must be inserted from above.
The mains lead must be placed along the left side of the housing (observe
EMC zone boundary).
Signal and control lines must only be fed into the housing on the right from
above or from the rear.
Batteries must be installed so that they cannot leak.
No cable openings should be made in the base of the housing, unless an
additional housing is mounted below the station to accommodate the batteries.