Installing, exchanging and connecting modules
Connection module (card cage)
7
168 | 248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
7.16 Connection module (card cage)
7.16.1 Installation
This component is installed in exactly the same way as for the operating units
with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027.
The connection module (card cage) FCA2006-A1 is always needed in conjunction
with the card cage (2 slots) or card cage (5 slots). It is fitted in the corresponding
fire control panels the factory and only has to be replaced in the event of a repair.
Figure 96: Installation of connection module (card cage)
1 Spacers (2 pieces)
2 Connection module (card cage)
3 Operating unit
4 Fixing screws (2 pieces)
X11 Connector for connection module (card cage)
X500 Module bus cable connection
1. Attach the connection module (card cage) (2) to the connector intended for it
(X11) on the operating unit (3) as shown.
2. Fasten the module to the spacers (1) using the two screws (4).
3. Connect the flat cable for the module bus of X500 connection module with
X501 on card cage.
3
4
1
2
X11
X500