Installing, exchanging and connecting modules
Ethernet switch FN2008 and safety module FN2009
7
139 |
248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
Fiber optic cable wiring
The accessible laser radiation is harmless. It corresponds to Laser Class 1 in
accordance with IEC 60825/ANSI Z136.
The fiber optic cable is wired cross-wise:
The optical transmitter (TX) of one device must always be connected
with the optical receiver (RX) of the other device.
Line 1 must always be connected with line 2.
The bending radius of the fiber optic cable must not be less than the
manufacturer's specification (e.g., 10 x external diameter).
Standard (PC) cable termination is sufficient, polish (APC) is not necessary,
but is supported.
7.14 Ethernet switch FN2008 and safety module FN2009
The installation description for these modules for extended networking relates to
the following modules, which are identical in construction:
Ethernet switch (MM) FN2008-A1
Security module (firewall) FN2009-A1
You will find detailed technical information on the corresponding data sheet or in
the technical description provided by the manufacturer.
7.14.1 Installing the mounting kit
The mounting kit is needed to install the modules for extended networking laterally.
Mounting kit FHA2029-A1
For all empty housings for wall mounting
For stations in Comfort housings
The modules have to be mounted horizontally or laterally in these housings as
there is insufficient installation depth.
The mounting kit FHA2029 consists of the following components:
Angle plate for installing in the housings
Two U-rails TS35, L 65 mm
Two retaining brackets for fixing on the side
Various mounting material
Cable kit and connection cable RJ45
A maximum of two modules can be installed on the angle plate.
Mounting kit FHA2030-A1
For stations in Large housings with enough free space
For the FC2080 in the housing (19", pedestal cabinet)
The modules can be installed standing on the DIN rails in the Large and Large
Extension housings, as well as in the 19" pedestal cabinets, and do not require an
angle plate.
The mounting kit FHA2030 consists of the following components:
Various mounting material
Cable kit and connection cable RJ45