Installing, exchanging and connecting modules
7
88 | 248
7.3.2 Pin assignments
Inputs and outputs which are not used do not require termination.
C-NET detector lines which are not used must not be terminated.
7.3.2.1 X1 supply
Pin Designation Description
1 #BATT Message input from the power supply: Battery fault
2 #CONV Message input from the power supply: Converter fault
3 #MAINS Message input from the power supply: Mains failure
4 COMMON Ground
5 3SRC+ Third power supply input (+) [FR]
6 3SRC– Third power supply input (–) [FR]
7 VSYS+ Supply input from the power supply (+)
8 VSYS+ Supply input from the power supply (+)
9 VSYS– Supply input from the power supply (–)
10 VSYS– Supply input from the power supply (–)
Admissible cable cross-section: 0.2…2.5 mm²
3SRC
-
#CONV
#BATT
-
VSYS
-