Loading...
Install
ing, exchanging and connecting modules
Loop extension
7
117 |
248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
Figure 59: Installing a loop extension with the example of the periphery board (2-loop)
1 Mounting holes on periphery board
2 Spacer bolts
3 Fixing screws
4 Loop extension (C-NET) FCI2003-A1
5 Loop extension connector to the periphery board
X13 Loop 3 connection terminal
X14 Loop 4 connection terminal
1. First, remove the relevant fixing screws (3) from the periphery board.
2. Screw the two spacer bolts (2) into the mounting holes (1) on the periphery
board.
3. Mount the loop extension (C-NET) onto the connector (5) on the periphery
board.
4. Screw the loop extension (C-NET) in place using the two fixing screws (3).
5. Wire up the detector lines according to the pin assignment.
X13
X14
1
2
3
4
5
X14