Installing, exchanging and connecting modules
Fire brigade periphery module [DE]
7
125 |
Building Technologies
X3 fire brigade operating panel
PIN Designation Description
8 Bf St ab Fire controls off
7 Ak Sign ab Acoustic signals off
6 BMZ rueckst Reset fire control panel
5 ↑ UE ab ↑ Remote transmission off
4 UE pruefen Check remote transmission
3 Reserve Reserve output
2 Reserve Reserve input
1 Not used
Admissible cable cross-section: 0.2…1.5 mm²
1 The connection details correspond to the FBF Type Wiesmeier FBF0770
2 Only switch possible
5
6
X2
LA ausgel
UE ausgel
7
8
0V
+24V
1
2
3
4
5
6
X3
UE ab
BMZ rueckst
7
8
Ak Sign ab
Bf St ab
1
2
3
4
Bf St ab
Ak Sign ab
BMZ rueckst
UE ab
UE pruefen
Reserve
Reserve
+
-
1
2
3
4
5
6
7
8
9
10
11
12