ng, exchanging and connecting modules
Ethernet switch FN2008 and safety module FN2009
7
146 | 248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
NOTICE
Loop with Ethernet cable
Impairment of system function
Pay attention to the Ethernet cable connection if you are connecting more
than one PMI & mainboard.
Never connect a port P1…P4 to a port P1…P4.
FT724 Fire terminal with optional power supply and batteries
FH7201-
Z3
Empty Eco housing
FDCIO222 I/O module (any I/O module possible)
LINE+
LINE-
C-NET loop connection
IN 1 Control input on separate I/O module (e.g. FDCIO222)
1 Connection for detector contact (F1, F2)
1
R
p
Parallel resistor for I/O module
2
P1…P4 Electric Ethernet connections
L1+, (L2+) Vsys + system supply from fire terminal board
3
M1, (M2) Vsys - system supply from fire terminal board
3
1
The detector contact is normally wired on a free I/O connection of the periphery
board. If all connections are occupied or if using the FT724 fire terminal, the
detector contact must be connected via an I/O module (e.g. an FDCIO222). In this
instance, the signal of the I/O module must not be configured as 'Degraded alarm
relevant'.
If a station is located very close to the FT724 fire terminal, the detector contact can
also be wired directly to this station.
2
The parallel resistor for the detector contact depends on the I/O module used.
Refer to the documentation provided with the I/O module used for more details.
3
Use of the redundant L2+/M2 supply inputs is optional and not necessary for EN-
54 compatibility.