Installing, exchanging and connecting modules
Operating add
-
on with 20 zones EVAC
-
NL [NL]
7
220 | 248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
Figure 132: Detail view of the hinge of the operating add-on
1 Cut-out section on the rear panel for the hinge
2 Hinge
3 Screw for securing the hinge
1. Remove cover from fire control panel.
2. Remove empty operating add-on.
3. From the rear, hang the new operating add-on FCM7221-H3 into the openings
in the rear panel of the housing (1) with the hinges (2).
4. Hold the operating add-on in place and secure the hinge (2) with the
screws (3).
5. Connect ribbon cable (X402) for peripheral data bus with periphery board
(X400 or X401).
6. Use the following tables to check the address setting.
7. Swivel the operating add-on towards the station and secure it using the four
screws.