Installing, exchanging and connecting modules
Door contact kit [DE]
7
240 | 248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
7.33.2.1 X6 intrusion detection system / local alarm / identification
lamp
Pin Designation Description
8 Ke Leuchte + Identification lamp (+)
7 Ke Leuchte - Identification lamp (-)
6 Oertl Alarm + Local alarm (+)
5 Oertl Alarm - Local alarm (-)
4 - Not used
3 FSD sabotage, closer (normally open)
2 FSD sabotage, common
1 FSD sabotage, opener (normally open)
Admissible cable cross-section: 0.2…1.5 mm²
1* Horn or beacon
2*
FSD sabotage, connection for "Transmission intrusion detection system"
(can be connected as NO or NC)
3* If necessary
5
6
X6
Oertl Alarm -
Oertl Alarm +
7
8
Ke Leuchte -
Ke Leuchte +
2
3
4
2
1
-
+
-
+
40 ... 2k
Ω Ω
1*
2*
2*
3*
300mA / max. 7.5W
560
2W
Ω
3*