Mounting and installing extinguishing control panels
Card cage connections (1 sector exting.) FCA2046
6
60 | 248
INPUT_MON_TYPE_2: ''Loss of agent' closed during pressure'
● ''Loss of agent' closed during pressure'
● Maximum line resistance 160 Ω (pressure gauge, cable, and plug)
● The maximum number of pressure gauges is calculated according to the max.
line resistance
Figure 34: MON_INPUT_TYPE, ''Loss of agent' closed during pressure'
Resistance range Input status
0000…0249 Ω SHORT (Fault)
0250…0519 Ω QUIET
0520…0799 Ω QUIET
0800…1099 Ω QUIET
1100…1499 Ω QUIET
1500…3999 Ω ACTIVE 1
≥4000 Ω OPEN (Fault)
INPUT_MON-
Manometer
normally closed
under pressu
re
N
1 2 3