Loading...
Mounting and installing extinguishing control panels
Card cage connections (1 sector exting.) FCA2046
6
63 |
248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
INPUT_MON_TYPE_5: ''Loss of agent' open during pressure'
Maximum line resistance 100 Ω (pressure gauge, cable, and plug)
The maximum number of pressure gauges (n) is calculated according to the
max. line resistance
Figure 37: MON_INPUT_TYPE, ''Loss of agent' open during pressure'
Resistance range Input status
0000…0249 Ω SHORT (Fault)
0250…0519 Ω SHORT (Fault)
0520…0799 Ω ACTIVE 1
0800…1099 Ω ACTIVE 1
1100…1499 Ω OPEN (Fault)
1500…3999 Ω QUIET
4000 Ω OPEN (Fault)