Mounting and installing extinguishing control panels
Card cage connections (1 sector exting.) FCA2046
6
70 | 248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
Monitored output type LOAD PYRO
Use Pyrotechnic valves
Monitoring polarity Normal polarity
Monitoring Only in inactive state
Calibration Yes
2-way monitoring Only permitted without 2-way connection box
Total load resistance, incl. cable
2…32 Ω,
max. 10 pyrotechnic valves, 25.8 V / 0.8 A
Max. cable resistance
Depending on number of valves (see valve
data sheet)
Monitoring tolerance ± 5 Ω, ± 1.2 Ω
A maximum of 10 pyrotechnic valves can be switched in series.
OUT_MON+
OUT_MON-
Pyrotechnic
actuators