Mounting and installing extinguishing control panels
Extinguishing terminal installation and wiring
6
77 |
Building Technologies
6.4.2.4 Extinguishing terminal wiring
Figure 42: Wiring diagram of the primary and secondary extinguishing terminals
Primary terminal
● A maximum of 1 primary terminal may be connected; the address must always
be '1'
● The maximum cable length for the primary terminal is 10 m; twisted and
unshielded cable with min. 7 twists/meter.
The polarity must be observed (A, B) whe
n connecting the data cable.
Secondary terminal
1) The maximum length of the stubs is 20 m for the secondary terminal
2) The line must be terminated at the furthest terminal with 120 Ω (secondary
terminals only)
3) An external power supply, e.g., FP120, is required for long lines or when if back-
up batteries are used.
● The address must always be ≥2; a maximum of 5 secondary terminals must be
connected for each extinguishing card.
● The maximum cable length for the secondary terminal is 1200 m; twisted and
unshielded cable with min. 7 twists/meter.
When using shielded cables, the shielding must be connected on the terminal
side.
● The cable resistance and the capacity is max. 80 Ω (on both sides) and max.
200 nF.