EasyManua.ls Logo

Siemens FS720 - Page 83

Siemens FS720
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing, exchanging and connecting modules
Periphery board (2
-
loop)
7
83 |
248
Building Technologies
A6V10210390_m_en_
--
Fire Safety
2018
-
-
29
7.2.2.2 X6 Horn, alarm and fault monitored outputs
Pin Designation Description
6 FAU_OUT Output fault
5 VSYS_O Supply output for consumer fault
4 AL_OUT- Alarm output (-)
3 AL_OUT+ Alarm output (+)
2 SOUND1- Horn output (-)
1 SOUND1+ Horn output (+)
Admissible cable cross-section: 0.2…1.5 mm²
1 Remote transmission
7.2.2.3 X7 RT alarm and RT fault changeover contacts
Pin Designation Description
6 FAU_NC RT fault normally closed contact
5 FAU_COM RT fault center tap (common)
4 FAU_NO RT fault normally open contact
3 AL_NC RT alarm break contact (normally closed)
2 AL_COM RT alarm center tap (common)
1 AL_NO RT alarm make contact (normally open)
Admissible cable cross-section: 0.2…1.5 mm²
1 Remote transmission
FAU_… Diagram of relay in normal operation = contact 5/4 closed
AL_… Diagram of relay in normal operation = contact 2/3 closed

Table of Contents

Other manuals for Siemens FS720

Related product manuals