Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
163 Operating hours when unit is live 1 Std_s32 Read only 0 h 9999999 h 1 h 0 h Info / Service
164 Number of startups resettable 1 Std_s32 Reset 0 9999999 1 0 Info / Service
165 Number of startups 1 Std_s32 Read only 0 9999999 1 0 Info / Service
166 Total number of startups 1 Std_s32 Read only 0 9999999 1 0 Info / Service
167 Fuel volume resettable [m³, l, ft³, gal] 1 Std_s32 Reset 0 99999999 1 0 Info / Service
172 Fuel 1: Operation hours resettable 1 Std_s32 Reset 0 h 9999999 h 1 h 0 h Info / Service
174 Fuel 1: Number of startups resettable 1 Std_s32 Reset 0 9999999 1 0 Info / Service
175 Fuel 1: Number of startups 1 Std_s32 Read only 0 9999999 1 0 Info / Service
177 Fuel 1: Fuel volume resettable (m³, l, ft³, gal) 1 Std_s32 Reset 0 99999999 1 0 Info / Service
186 Software drop out delay of flame signal (100 ms)
Index = = QRB... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
2 Std_u8 Edit 0 20 1 0; 0 OEM
187 Fuel 1: Software drop out delay of flame signal (100 ms)
Index = = QRB... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
2 Std_u8 Edit 0 20 1 0; 0 OEM
190 Postpurging in lockout position
0 = deactivate (no-load position)
1 = active (postpurge position)
When active, the
Alarm in the event of start prevention function is only
possible to a limited extent!
1 Selection Edit 0 1 1 0 SO
194 Repetition limit no flame at the end of safety time (TSA)
1 = no repetition
2...4 = 1...3 repetitions
3 Std_u8 Edit 1 2 1 0 OEM
196 Repetition limit air pressure failure
1 = no repetition
2 = 1 repetition
1 Std_u8 Edit 1 16 1 3 OEM
200 Basic unit
201 Burner operating mode (fuel train, modulating / multistage, actuators,
etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
1 Selection Edit / clear 1 27 1 undefined SO