217/248 
Building Technologies Division  Basic documentation LMV36...  CC1P7544en 
Infrastructure & Citiies Sector  29 Parameter list LMV36...  25.09.2013 
Par.  Parameter  Number of  Type  Edit  Value range  Resolution  Default  Password level 
no.  LMV36...  elements      Min  Max    setting   
163  Operating hours when unit is live  1  Std_s32  Read only  0 h  9999999 h  1 h  0 h  Info / Service 
164  Number of startups resettable  1  Std_s32  Reset  0  9999999  1  0  Info / Service 
165  Number of startups  1  Std_s32  Read only  0  9999999  1  0  Info / Service 
166  Total number of startups  1  Std_s32  Read only  0  9999999  1  0  Info / Service 
167  Fuel volume resettable [m³, l, ft³, gal]  1  Std_s32  Reset  0   99999999   1   0   Info / Service 
172  Fuel 1: Operation hours resettable  1  Std_s32  Reset  0 h  9999999 h  1 h  0 h  Info / Service 
174  Fuel 1: Number of startups resettable   1  Std_s32  Reset  0  9999999  1  0  Info / Service 
175  Fuel 1: Number of startups  1  Std_s32  Read only  0  9999999  1  0  Info / Service 
177  Fuel 1: Fuel volume resettable (m³, l, ft³, gal)  1  Std_s32  Reset  0   99999999   1   0   Info / Service 
186  Software drop out delay of flame signal (100 ms) 
Index = = QRB... (0 = inactive, >1) 
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps) 
2 Std_u8 Edit 0  20 1  0; 0  OEM 
187  Fuel 1: Software drop out delay of flame signal (100 ms) 
Index = = QRB... (0 = inactive, >1) 
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps) 
2 Std_u8 Edit 0  20 1  0; 0  OEM 
190  Postpurging in lockout position 
0 = deactivate (no-load position) 
1 = active (postpurge position) 
 
When active, the 
Alarm in the event of start prevention function is only 
possible to a limited extent! 
1 Selection Edit 0  1  1  0  SO 
194  Repetition limit no flame at the end of safety time (TSA) 
1 = no repetition 
2...4 = 1...3 repetitions 
3 Std_u8 Edit 1  2  1  0  OEM 
196  Repetition limit air pressure failure 
1 = no repetition 
2 = 1 repetition 
1 Std_u8 Edit 1  16 1  3  OEM 
         
200  Basic unit 
               
201  Burner operating mode (fuel train, modulating / multistage, actuators, 
etc.) 
-- = undefined (delete curves) 
1 = G mod 
2 = Gp1 mod 
1 Selection Edit / clear 1  27 1  undefined  SO