Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
211 Fan ramp up time 1 Time Edit 2 s 60 s 0.2 s 2 s SO
212 Max. time down to low-fire 1 Time Edit 0.2 s 10 min 0.2 s 45 s SO
213 Waiting time home run 1 Time Edit 2 s 60 s 0.2 s 2 s OEM
214 Max. time start release 1 Time Edit 0.2 s 10 min 0.2 s 35 s OEM
215 Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
1 Std_u8 Edit 1 16 1 1 SO
217 Max. waiting time for detection of detector or pressure signal (e.g.
home run, preignition «Lo»)
1 Time Edit 5 s 10 min 0.2 s 30 s OEM
221 Gas: Active detector flame evaluation
0 = QRB
1 = ION / QRA
1 Selection Edit 0 1 1 1 SO
222 Gas: Prepurging
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO
223 Repetition limit gas pressure switch-min
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
1 Std_u8 Edit 1 16 1 1 SO
225 Gas: Prepurge time 1 Time Edit 5 s 60 min 0,2 s 30 s SO
226 Gas: Preignition time 1 Time Edit 0.4 s 60 min 0,2 s 2 s SO
227 Gas: Safety time 1 (TSA1) 1 Time Edit 1 s 10 s 0,2 s 5 s OEM
229 Gas: Time to respond to pressure faults within safety time 1 (TSA1)
and safety time 2 (TSA2)
1 Time Edit 0.4 s 9.6 s 0,2 s 1,8 s OEM
230 Gas: Interval 1 1 Time Edit 0.4 s 60 s 0,2 s 2 s SO
231 Gas: Safety time 2 (TSA2) 1 Time Edit 1 s 10 s 0,2 s 7 s OEM
232 Gas: Interval 2 1 Time Edit 0.4 s 60 s 0,2 s 2 s SO
233 Gas: Afterburn time 1 Time Edit 0.2 s 60 s 0.2 s 8 s SO
234 Gas: Postpurge time (no extraneous light test) 1 Time Edit 0.2 s 108 min 0.2 s 15 s SO
235 Gas: Air pressure switch (LP)
0 = inactive
1 = active
2 = active, except phase 60...66 (pneumatic operation only)
1 Selection Edit 1 2 1 1 SO