113/213
Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 15 Special feature: Identification of burner (ID) 01.12.2009
15 Special feature: Identification of burner
(ID)
The OEM must assign an individual burner identification to every burner. This ensures
that during backup / restore, incompatible parameter sets cannot be copied between dif-
ferent burners (also refer to documentation on PC tool under
Backup / Restore and in
this documentation in chapter
Backup / Restore).
No. Parameter
113 Burner identification
16 Connection to superposed systems
16.1 General and functions of building automation
system
Communication with a building automation and control system is accomplished via a
data link using the COM X92 port and a special interface with galvanic separation and
physical bus level adaptation. This port can be used for connection of a Modbus, de-
pending on the configuration made.
OCI412.10
RS485
Modbus
LMV...
COM
X92
Figure 54: Connection via interface COM 92 to superposed systems
&
Note
Breakdown of bus communication.
If the basic unit detects a breakdown of bus communication, the BAC system must re-
write the following values upon restoration of communication:
• Modbus: The Modus, Modbus operating mode and predefined target output
General setting values for connection of the basic unit to the BAC system (for factory
settings, refer to the parameter list):
Bus communication may only be interrupted for the time set.
If communication is disturbed for a longer period of time, the LMV37.4... basic unit deliv-
ers a fault status message and the values set in the basic unit by the BAC system will
be reset.