26.11.2 Setting curvepoints P0 and P9 for modulating modeG mod», «Gp1
mod», «Gp2 mod» and «Lo mod»)
&
Note
Not all actuators used in the following example can be set, depending on the selected
operating mode.
Example of «G mo
P
Vh
mi n
s%
Bild 102/0707
Display
P0 appears flashing.
Curvepoint for ignition load.
F
P
Vh
mi n
s%
Bild 103/0707
Keep
F depressed.
You are now in setting
P0 of fuel setting F for
ignition position
P0.
F
and
or
P
Vh
mi n
s%
Bild 104/0707
Press simultaneously
F and or to
set ignition position
P0 of the fuel damper.
Example:
30.0
P
Vh
mi n
s%
Bild 105/0707
Release
F .
The selected value is adopted.
Example:
30.0
A
P
Vh
mi n
s%
Bild 106/0707
Keep
A depressed.
You are now in setting
P0 of air actuator A for
ignition position
P0.
A
and
or
P
Vh
mi n
s%
Bild 107/0707
Press simultaneously
A and or to
set ignition position
P0 of the air actuator.
Example:
22.0
P
Vh
mi n
s%
Bild 108/0707
Release
A .
The selected value is adopted.
Example:
22.0
F
and
A
P
Vh
s
min %
Bild 1 09/08 07
Keep
F and A depressed.
You are now in setting
n0, speed n is for ignition
position
n0