160/213 
Building Technologies  Basic documentation LMV37.4...  CC1P7546en 
HVAC Products  26 Parameter level  01.12.2009 
26.11.2  Setting curvepoints P0 and P9 for modulating mode («G mod», «Gp1 
mod», «Gp2 mod» and «Lo mod») 
 
& 
Note 
Not all actuators used in the following example can be set, depending on the selected 
operating mode. 
 
Example of «G mod» 
 
 
P
Vh
mi n
s%
Bild 102/0707
 
Display
 P0 appears flashing. 
 
Curvepoint for ignition load. 
 
F
 
P
Vh
mi n
s%
Bild 103/0707
 
Keep 
F  depressed. 
 
You are now in setting 
P0 of fuel setting F for 
ignition position 
P0. 
 
F
 
and 
 or   
P
Vh
mi n
s%
Bild 104/0707
 
Press simultaneously 
F  and   or   to 
set ignition position 
P0 of the fuel damper. 
 
Example: 
30.0 
 
 
P
Vh
mi n
s%
Bild 105/0707
 
Release
F . 
 
The selected value is adopted. 
 
Example: 
30.0 
 
A
 
P
Vh
mi n
s%
Bild 106/0707
 
Keep 
A  depressed. 
 
You are now in setting 
P0 of air actuator A for 
ignition position 
P0. 
 
A
 
and 
 or   
P
Vh
mi n
s%
Bild 107/0707
 
Press simultaneously 
A  and   or   to 
set ignition position 
P0 of the air actuator. 
 
Example: 
22.0 
 
 
P
Vh
mi n
s%
Bild 108/0707
 
Release
A . 
 
The selected value is adopted. 
 
Example: 
22.0 
 
F
 and 
A
 
P
Vh
s
min %
Bild  1 09/08 07
 
Keep 
F  and  A  depressed. 
You are now in setting 
n0, speed n is for ignition 
position 
n0