22.1.4 Fault status message, display of errors and info
22.1.4.1. Display of errors (faults) with lockout
P
Vhmins%
Bi ld 1 7/0707
P
Vhmins%
Bi ld 1 8/0707
The display shows
Loc:, the bar under the fault status
message
appears.
The unit is in the lockout position.
The display shows current error code
c: alternating with
diagnostic code
d: (refer to Blink code list).
Example: Error code
4 / diagnostic code 3
22.1.4.2. Reset
reset
1...3 s
P
Vhmins%
Bi ld 1 9/0707
When pressing
reset
for 1...3 s, rESEt appears on the dis-
play.
When the button is released, the basic unit is reset.
If the
reset
button is pressed for a time other than the time
indicated above, a change to the previous menu is made.
Exception
If an error occurred while setting the curve, a change back
to the parameter setting level is made.
22.1.4.3. Activating info / service mode from lockout
reset
>3 s
P
Vhmins%
Bi ld 2 0/0707
reset
>5 s
P
Vhmins%
Bild 2 1/0707
reset
>8 s
P
Vhmins%
Bild 2 2/0707
When pressing
reset
for >3 s, the display shows InFo, SEr
and then
OPErAtE.
When the button is released, a change to info / service
mode is made.