Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 26 Parameter level 01.12.2009
26.9 Parameter with index, with direct display
26.9.1 Using the example of parameter 501: Non-flame positions fuel actuator
P
Vhmins%
Bild 75/0707
PArAmeter level 500: for air-fuel ratio
control.
/
reset
P
Vh
mi n
s%
Bild 76/0707
Press
/
reset
to go to menu level 500:.
Display: Parameter
501. flashes, index 00:
and value
0.0 do not.
/
reset
P
Vh
mi n
s%
Bild 77/0707
Press
/
reset
to go to the index.
Display: Parameter
501. does not flash, index
00: flashes, value 0.0 does not.
or
P
Vh
mi n
s%
Bild 78/0707
Press
or to select the required
index.
.00 = no-load position
.01 = prepurge position
.02 = postpurge position
Display: Index
01: for prepurge position flas-
hes, value
0.0 does not.
/
reset
P
V
hmins %
Bild 79/0707
Press
/
reset
to go to editing mode.
Display: Value
0.0
or
P
Vh
mi n
s%
Bild 80/0707
Press
or to select the required
prepurge position.
Example:
1.0