Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 26 Parameter level 01.12.2009
P
Vhmins%
Bild 94/0707
As soon as symbol or is no longer high-
lighted, you can press
Esc a second time.
ESC
P
Vh
mi n
s%
Bild 128/070 7
The “warm settings for air-fuel ratio control by the LMV37.4... are now completed.
26.11.5 Warm settings for modulating modeG mod pneu», «Gp1 mod pneu»
and «Gp2 mod pneu»)
&
Note
Refer to subsection Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)! Here, only the air must be adjusted with A .
26.11.6 Cold settings for «G mod», «Gp1 mod», «Gp2 mod» and «Lo mod»
&
Note
Refer to subsection Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)! With no flame, however, no actuator travel and no automatic operation after
the settings have been made.
26.11.7 Cold settings for «G mod pneu», «Gp1 mod pneu» and «Gp2 mod
pne
&
Note
Refer to subsection Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod»
and «Lo mod»)! With no flame, however, no actuator travel and no automatic operation after
the settings have been made. Here, only the air must be adjusted with A .