Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 21 Operating the AZL2… unit 01.12.2009
21.6.2 Restore
Parameter
000: blinks.
Display: Parameter
000: blinks, Int does not.
/
reset
Only
OEM
level
Press
/
reset
to go to parameter group 041.
Display: Parameter
041: blinks, ._._ does not.
Press
to select parameter 050
Display: Parameter
050. blinks, index 00: and value 0 do
not.
/
reset
7548z358/1009
Press
/
reset
to go to parameter bAC_UP
Display: Parameter
bAC_UP
7548z359/1009
Press
to select parameter rEStorE
Display: Parameter
rEStorE
/
reset
Press
/
reset
to select the restore process.
Display: Value
0
Press to shift the value in change mode by one posi-
tion to the left.
Display: Value
1 blinks.
Note
To detect potential display errors, the value is displayed
one position shifted to the left.