Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 10 Actuators X53 / X54 01.12.2009
10.5 Monitoring the positions
To monitor the actuator’s actual positions, an optical incremental transducer with a reso-
lution of 0.7° is used. The correct position of the drive shaft is ensured by comparing the
motor steps made with the position obtained from the incremental transducer. Due to
the different resolutions of motor steps and incremental transducer plus the selected tol-
erance band, the following error identification band is obtained. The decision where, in
the error identification band, shutdown takes place depends on the currently required
position.
For the default setting made in the factory, the error detection band is as follows:
Smallest position error where an error can be detected 1.
Greatest position error where an error is securely detected (default setting
parameter 606)
1.
The presetting of 1.7° (default setting, parameter 606) is suited for use with actuators
type SQN1... and SQM3...
Note
When using SQN1… actuators equipped with plastic gear trains, we recommend to
change the preset values as follows:
Type Value
SQN13.14... 1,7°
SQN14.14... 1,7°
SQN13.17... 2,2°
&
SQN14.17... 2,2°
When referencing under output conditions, the resilience of the actuator’s gear train
must also be taken into consideration:
Type
reference
Resilience at max.
rated driving
torque
SQM33.41... 0.2°
SQM33.51... 0.2°
SQN13.14... 0.3°
SQN13.17... 0.8°
SQN14.14... 0.3°
SQN14.17... 0.8°
The error detection time is <1 second.
Caution!
This means that – for the design and setting of the burner – a position error re-
sulting from the sum of
- greatest position error from which an error is detected in all positions
- resilience at the max. rated torque
- mechanical influence from the link between actuator and regulating unit
(e.g. coupling)
must not lead to a critical state in terms of safety.
No. Parameter
606
Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
Error detection band: (P606 -0.6°) up to P606
Error
code
Diagnostic
code
Meaning for the LMV37.4... system
86 0 Position error fuel actuator
87 0 Position error air actuator