180/213
Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 27 Parameter list LMV37.4... 01.12.2009
27 Parameter list LMV37.4...
Par.
Parameter Number of Type Edit Value range Resolution Default Password level
no. elements Min Max setting
000 Internal parameters
041 Password heating engineer (4 characters) 1 Std_u16 edit 0 65535 1 OEM
042 OEM password (5 characters) 1 Std_u16 edit 0 65535 1 OEM
050 Start backu
/ restore via AZL2.../ PC tool
set
arameter
to 1)
Index 0: Create backup
Index 1: Execute restore
Error diagnostics via negative values (see error code
137)
2 Std_s8 edit -99 2 1 0; 0 SO
055 Burner identification of AZL2... backup data set 1 Std_s32 read only 0 99999999 1 0 SO
056 ASN extraction of AZL2... backup data set 8 Std_u8 read only 0 127 1 0 SO
057 Software version when creating the AZL2... backup data
set
1 Hex_16 read only 0x100 0xFFF9 1 0 SO