158/213
Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 26 Parameter level 01.12.2009
&
Note
Ensure that the fuel train is correctly set in accordance with the type of burner.
No. Parameter Actuator controlled
201 Burner operating mode (fuel train, modulating / multistage,
actuators, etc.)
Air Fuel
-- = undefined (delete curves) X X
1 = gas modulating (G mod) X X
2 = gas modulating with pilot valve (Gp1 mod) ¹) X X
3 = gas modulating with pilot valve (Gp2 mod) ¹) X X
4 = oil modulating (Lo mod) X X
5 = oil 2-stage (Lo 2 stage) X ---
6 = oil 3-stage (Lo 3 stage) ¹) X ---
7 = gas modulating (G mod pneu) X ---
8 = gas modulating (Gp1 mod pneu) ¹) X ---
9 = gas modulating (Gp2 mod pneu) ¹) X ---
10 = oil modulating with gas pilot (LoGp mod) X X
11 = oil 2-stage with gas pilot (LoGp 2-stage) X ---
12 = oil modulating with 2 fuel valves (Lo mod 2V) X X
13 = oil modulating with gas pilot and 2 fuel valves
(LoGp mod 2V)
X X
14 = gas modulating (G mod pneu, 0 active) --- ---
15 = gas modulating with pilot (Gp1 mod pneu, 0 active) --- ---
16 = gas modulating with pilot (Gp2 mod pneu, 0 active) --- ---
17 = oil 2-stage (Lo 2-stage, 0 active) --- ---
18 = oil 3-stage (Lo 3-stage, 0 active) --- ---
19 = gas modulating only when fired on gas
(G mod fuel active)
--- X
20 = gas modulating with pilot only when fired on gas
(Gp1 mod fuel active)
--- X
21 = gas modulating with pilot only when fired on gas
(Gp2 mod fuel active)
--- X
22 = oil modulating only when fired on oil
(Lo mod fuel active)
--- X