182/213 
Building Technologies  Basic documentation LMV37.4...  CC1P7546en 
HVAC Products  27 Parameter list LMV37.4...  01.12.2009 
 
Par. 
Parameter  Number of  Type  Edit  Value range  Resolution  Default  Password level 
no.    elements      Min  Max    setting   
130  Delete display of error history 
To delete the display: Set parameter to 1, then to 2 
Return value 0: Job successfully completed 
Return value -1: Timeout of 1_2 sequence 
1 Std_s8 edit -5 2 1 0  SO 
133  Default output for TÜV test 
Invalid = TÜV test when output is acti ve 
2.000...10.000 = low-fire...high-fire or stage 1 / stage 2 / 
stage 3 
1  Output  edit / clear  20 %  100 %  0.1 %  undefined  SO 
141  Operating mode BACS 
0 = off 
1 = Modbus 
2 = reserved 
1 Selection edit 0 2 1 0  SO 
142 
Setback time in the event of communication breakdown 
 
Setting values 
0 = inactive 
1….7200 s 
1  Std_u16  edit  0 s  7200 s  1 s  600 s  SO (BA) 
143 Reserved  1 Std_u8 edit 1 8 1 1  Info / Service 
144  Reserved  1  Std_u16  edit  10 s  60 s  1 s  30 s  SO 
145 
Device address for Modbus of basic unit 
 
Setting values 
1…247 
1 Std_u8 edit 1  247 1  1  SO 
146 
Setting of Baud rate for Modbus communication 
 
Setting values 
0 = 9600 
1 = 19200 
1 Selection edit 0 1 1 1  SO 
147  Parity for Modbus 
0 = none 
1 = odd 
2 = even 
1 Selection edit 0 2 1 0  SO