HVAC Products 28 Error code list 01.12.2009
Error
code
Diagnostic code Meaning for LMV37.4... system Recommended measures
83 # Speed error VSD
Required speed has not been reached
Bit 0
Valency 1
Lower control range limitation
Speed has not been reached because control range limitation has become active
for measures, refer to error code 80
Bit 1
Valency 2...3
Upper control range limitation
Speed has not been reached because control range limitation has become active
for measures, refer to error code 80
Bit 2
Valency 4...7
Interrupt shutdo wn due to electromagnetic interference
Speed has not been reached due to too much electromagnetic interference on the sensor line
for measures, refer to error code 81
Bit 3
Valency
8
Curve too steep in terms of ramp speed
Speed has not been reached because detected curve slope was too steep.
1. With a LMV3... ramp of 20 s, the curve’s slope may be a maximum of 10% speed change be-
tween 2 curvepoints in modulating mode.
With a LMV3... ramp of 10 s, the curve’s slope may be a maximum of 20% speed change between
2 curvepoints in modulating mode.
With a LMV3... ramp of 5 s, the curve’s slope may be a maximum of 40% speed change between
2 curvepoints in modulating mode.
Between the ignition point (P0) and the low-fire point (P1), the speed change in modulating
mode may be a maximum of 40%, independent of the LMV3… ramp.
2. The setting of the VSD ramp must be about 20% faster than the ramps in the basic unit
(parameters 522, 523).
Bit 4
Valency
16
Interruption of speed signal
No speed detected in spite of control.
1. Check if the motor turns.
2. Check if the speed sensor delivers a signal (LED / check distance from the sensor disk).
3. Check wiring of the VSD.
Bit 5
Valency
32
Quick shutdown due to excessive speed deviation
Speed deviation was for about 1 s >10% outside the anticipated range.
1. Check ramp times of the LMV37.4... and VSD.
2. Check wiring of the VSD.