205/213 
Building Technologies  Basic documentation LMV37.4...  CC1P7546en 
HVAC Products  28 Error code list  01.12.2009 
 
Error 
code 
Diagnostic code  Meaning for LMV37.4... system  Recommended  measures 
150 #  TÜV test   
  1 (-1)  Invalid phase 
TÜV test may only be started in phase 60 (operation) 
  2 (-2)  TÜV test default output too low 
TÜV test default output must be lower than the lower output limit 
  3 (-3)  TÜV test default output too high 
TÜV test default output must be higher than the upper output limit 
  4 (-4)  Manual abortion 
No error: Manual abortion of TÜV test by the user 
  5 (-5)  TÜV test timeout 
No loss of flame after fuel valves have been shut 
1. Check for extraneous light 
2. Check wiring for short-circuit 
3. Check to see if one of the valves is leaking 
165 #  Internal error 
 
166 
0  Internal error watchdog reset   
167 #  Manual locking 
Unit has been manually locked (no error) 
  1  Manual locking by contact   
  2  Manual locking by AZL2...   
  3  Manual locking by PC tool   
 8 
Manual locking by the AZL2... 
Timeout / communication breakdown 
During a curve adjustment via the AZL2..., the timeout for menu operation has elapsed (setting via 
parameter 127), or communication between the LMV37.4... and the AZL2... has broken down 
 9 
Manual locking by the PC tool 
Communication breakdown 
During a curve adjustment via the ACS410, communication between the LMV37.4... and the 
ACS410 was interrupted for more than 30 seconds 
 
33 
Manual locking after PC tool  
reset attempt 
PC tool made a reset attempt although the system worked correctly 
168  #  Internal error management 
Make a reset; if error occurs repeatedly, replace the unit 
169  #  Internal error management 
Make a reset; if error occurs repeatedly, replace the unit 
170  #  Internal error management 
Make a reset; if error occurs repeatedly, replace the unit 
171  #  Internal error management 
Make a reset; if error occurs repeatedly, replace the unit 
200 OFF  #  System error-free 
No error 
201 
OFF UPr 
# Start prevention 
Start prevention because unit has not been parameterized 
  1  No operating mode selected   
  2..3  No fuel train defined   
  4..7  No curves defined   
  8..15  Standardized speed undefined   
  16..31  Backup / restore was not possible