Building Technologies Basic Documentation LMV37.4... CC1P7546en
HVAC Products 29 Revision history of basic unit LMV37.4... 01.12.2009
Software version V02.90
Optimization: Indication of errors on the parameter and info / service menu
Optimization: Rectification of eBus error telegrams, correction of manufacturer’s
code for safety limit thermostat, extension of service data interrogation PB:03h
SB:10h by the meter readings of the second fuel, PB:05h SB:09h shows the fuel
currently burnt
Optimization: Curve setting invalid (OFF Upr) upon change to cold settings
Optimization: Setting of minimum / maximum output via the parameterized
output
Optimization: Shorter startup time with valve proving (prepurge or postpurge time
simultaneously with valve proving)
New function: Loss-of-flame test (V test), forced shutdown of fuel valves
Extension: Pressure switch-min-oil active from phase 38 or safety time (phase 40)
Extension: Setting of dead band zone for load controller contacts, analog input and
BACS output
Extension: POC for fired on oil (alternative to pressure switch-max)
New function: Valve proving via pressure switch-min
New function: Abortion of postpurging (see postpurge time, extraneous light test in
phase 78)
New function: Evaluation of load controller contacts for multistage operation (normal
/ interchanged)
New fuel trains LOGp, LO-2V, LOGp-2V
New operating modes (e.g. without actuator)
New function: Backup / restore via AZL2... (only with new software version AZL2...)
Software version V03.00
Optimization: Maximum time of safety phase reduced from 28 to 27 seconds