EasyManua.ls Logo

Siemens LOGO! 230 RC - Rainwater Pump with LOGO! 230 RC

Siemens LOGO! 230 RC
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
99
LOGO! manual
EWA 4NEB 712 6006-02
5.6.3 Rainwater pump with LOGO! 230RC
L1 N I1 I2 I3 I4 I5 I6
Q1 Q2 Q3 Q4
SIEMENS
K1 Y1
S4S3
L1
N
S1 S2
p<
LOGO! 230RC
Pump Drinking water supply
Apart from LOGO!, you need only the pressure switch and the float
switches to control the pump. If you are using a three-phase motor, you need
a master contactor. If the system has a single-phase motor, you need a con-
tactor if the motor requires more current than output relay Q1 can switch.
The consumption of a solenoid valve is so low that you can normally con-
trol it directly.
S K1 Master contactor
S Y1 Solenoid valve
S S1 Pressure switch
S S2 to S4 Float switches
Applications

Table of Contents

Related product manuals