EasyManua.ls Logo

Siemens LOGO! 230 RC - 2.3 Switching LOGO! on;resumption of power supply

Siemens LOGO! 230 RC
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LOGO! manual
EWA 4NEB 712 6006-02
10
2.3 Switching LOGO! on/resumption of power
supply
LOGO! does not have a power switch. How LOGO! responds when
switched on depends on:
S Whether a program is stored in LOGO!
S Whether a memory card is inserted
S The state LOGO! was in before power off
The table indicates LOGO!s responses to the possible situations:
If Then
LOGO! does not contain a program
and there is no memory card inserted
The following appears on LOGO!s dis-
play: No Program
LOGO! does not contain a program,
there is a memory card inserted, but the
card does not contain a program (empty
memory card)
The following appears on LOGO!s dis-
play: No Program
LOGO! does not contain a program,
there is no or an empty memory card
inserted, and
1. LOGO! was in RUN or in parame-
terization mode before power off
2. LOGO! was in programming mode
before power off LOGO!
LOGO! uses the stored program and
1. Goes into RUN
2. Goes into the main menu in pro-
gramming mode
A memory card containing a program
is inserted and
1. LOGO! was in RUN or in parame-
terization mode before power off
2. LOGO! was in programming mode
or No Program was displayed before
power off
LOGO! copies the program from the
memory card automatically and
1. Goes into RUN
2. Goes into the main menu in pro-
gramming mode
Installing and wiring LOGO!

Table of Contents

Related product manuals