LOGO! functions
4.4 Special functions list - SF
LOGO!
Manual, 04/2011, A5E03556174-01
205
4.4.16 Hours counter
Short description
A configured time is triggered with a signal at the monitoring input. The output is set when
this time has expired.
Symbol in LOGO! Wiring Description
Input R A positive edge (0 to 1 transition) at input R resets
output Q and sets a configured value MI at the
counter for the duration of the time-to-go (MN).
Input En En is the monitoring input. LOGO! scans the on-time
of this input.
Input Ral A positive edge at input Ral (Reset all) resets the
hours counter (OT) and the output, and sets the time-
to-go value (MN) to the maintenance interval MI:
Output Q = 0
Measured operating time OT = 0
Time-to-go of the maintenance interval MN = MI.
Parameter MI: Maintenance interval to be preset in units of hours
and minutes
Range of values:
0000...9999 h, 0...59 m
OT: The accumulated total operating time; you can
specify an offset in hours and minutes
Range of values:
00000...99999 h, 0...59 m
Q → 0:
When "R" is selected:
Q = 1, if MN = 0;
Q = 0, if R = 1 or Ral = 1
When "R+En" is selected:
Q = 1, if MN = 0;
Q = 0, if R = 1 or Ral = 1 or En = 0.
K
4
5
(Q
5DO
3DU
Output Q The output is set when the time-to-go MN = 0 (see
timing diagram).
The output is reset:
When "Q→0:R+En", if
R = 1 or Ral = 1 or En = 0
When "Q→0:R", if R = 1 or Ral = 1.
MI = Configured time interval
MN = Time-to-go
OT = Total time expired since the last hi signal at input Ral
These values are always retentive!